UPS calculator: what size UPS you need and how long it will last
List the equipment you want to keep running during a power cut. The calculator adds up the watts, suggests the VA and watt rating to look for and estimates the backup time from your batteries.
Equipment on the UPS
Example: the 180 W power supply of a Lenovo ThinkCentre M70s Gen 5.
Example: the 65 W adapter of a Lenovo ThinkPad E14 Gen 6.
Example: Lenovo ThinkVision T24i-30, 51 W maximum (14 W typical).
Example: MikroTik hAP ax², 12 W maximum without attachments.
Example: Dahua NVR4108HS-P-4KS3, under 10 W plus up to 36 W for its PoE cameras, disk not included.
Example: Epson TM-T20III, 1.8 A mean at 24 V, about 43 W.
Anything else on the UPS: take the watts from its label or datasheet.
UPS sizing
CyberPower suggests a UPS rated 20 to 30% above the total watts.
From the UPS label or datasheet. APC’s Back-UPS 1200VA, for example, is rated 650 W: a power factor of about 0.54.
Batteries, for the backup time
The amp-hours printed on the battery.
How much of the battery’s energy the UPS turns into mains power. Your assumption, unless the datasheet gives it.
Example values: change them to your own.
Your result
UPS rating to look for
At least 603 VA
and at least 362 W: your load plus 25% headroom, at a power factor of 0.6
Total load
289 W
Estimated backup time
16 min
A rough guide for new, fully charged lead-acid batteries. Before the correction for fast discharge: 38 min.
- Total load
- 289 W
- With headroom
- 362 W
- UPS rating in VA
- 603 VA
- Battery energy
- 216 Wh
- Simple backup time
- 38 min
- Corrected for fast discharge
- 16 min
The working
289 W × (1 + 25%) = 362 W, and 362 W ÷ 0.6 = 603 VA. 12 V × 9 Ah × 2 = 216 Wh. 216 Wh × 85% ÷ 289 W = 0.64 hours. Corrected for fast discharge: 20 × (0.64 ÷ 20)^1.25 = 0.27 hours.
Computer hardware
Laptops, desktops, servers, printers, networking, UPS, software and consumables from the brands you trust.

- Dell · HP · Lenovo · Canon
- Consumables & accessories
- Dealer price lists
- Tanzanian IT company since 2001
- Branch offices across Tanzania
Often bought together: Repairs, networking & AMC, CCTV security cameras
How it works
Watts (W) are the real power your equipment uses, and volt-amperes (VA) are the apparent power the UPS must supply. The ratio of the two is the power factor: CyberPower’s example is a UPS rated 1000 VA and 700 W, a power factor of 0.7. A UPS has a limit in both, so the calculator adds your headroom to the total watts and divides by the UPS’s power factor to give the VA to look for. CyberPower suggests a watt rating 20 to 30% above your total.
The preset watts are maximum or rated figures from the spec sheets of example models: a Lenovo ThinkCentre M70s Gen 5 desktop (180 W power supply), a ThinkPad E14 Gen 6 laptop (65 W adapter), a ThinkVision T24i-30 monitor (51 W maximum), a MikroTik hAP ax² router (12 W without attachments), a Dahua NVR4108HS-P-4KS3 recorder (under 10 W, plus up to 36 W of PoE for its cameras) and an Epson TM-T20III receipt printer (1.8 A mean at 24 V). Everyday use is often far lower: Lenovo lists that monitor at 14 W typical. Replace them with the figures for your own equipment.
Battery energy is volts × amp-hours × the number of batteries, in watt-hours, and the UPS turns most of it into mains power: that share is the efficiency you enter. Dividing by the load gives a simple backup time. But batteries deliver less when drained fast: Victron Energy’s example is a 100 Ah lead-acid battery, rated over 20 hours, that gives about 56 Ah when emptied in two hours. So the calculator applies Peukert’s law with the exponent of 1.25 that Victron calls an acceptable average for most lead-acid batteries: time = 20 × (simple time ÷ 20)^1.25.
Treat the backup time as a rough guide. Victron notes that the Peukert exponent is only an approximation and that at very high currents a battery can deliver even less, and older batteries hold less charge. For a firm figure, look up the runtime chart in your UPS maker’s datasheet for your load.
Assumptions
- The watts you enter are maximum or rated figures; real draw changes from moment to moment.
- Headroom is added to the total watts before dividing by the power factor to get VA.
- Batteries are lead-acid, new and fully charged, with amp-hours rated over 20 hours.
- The correction for fast discharge uses Peukert’s law with an exponent of 1.25, Victron’s default for lead-acid batteries.
This is an estimate based on the numbers you enter. It is not a quote or professional advice.
Questions
Add the watts of everything that will plug into the UPS, add 20 to 30% headroom as CyberPower suggests, and check the UPS is rated for that many watts and for the watts divided by its power factor in VA. A desktop with a 180 W power supply and a 51 W monitor make 231 W, so with 25% headroom look for at least 289 W and 482 VA at a power factor of 0.6.
Watts are the real power your equipment uses, and VA (volt-amperes) is the apparent power the UPS must deliver. The power factor is watts divided by VA, so a 1000 VA UPS with a power factor of 0.7 supplies at most 700 W, as CyberPower explains. Your load must stay within both ratings, which is why a UPS that looks big enough in VA can still be overloaded in watts.
It depends on the load and the batteries. Battery watt-hours (volts × amp-hours × number of batteries) times the UPS’s efficiency, divided by the load, gives a simple time, but lead-acid batteries deliver less when drained fast, so this calculator corrects for that with Peukert’s law. Battery age matters too. For a firm figure, check the runtime chart for your UPS model at your load.
Because battery amp-hours are rated over 20 hours, and a UPS empties its batteries in minutes. Victron Energy gives the example of a 100 Ah battery rated over 20 hours that delivers only about 56 Ah when discharged in two hours, and the loss grows at higher loads. Keeping only essential equipment on the battery outlets lowers the load and stretches the time.
More free tools
How to choose a UPS: VA and watts, UPS types, sizing and batteries
A UPS keeps computers running through short power cuts and lets servers shut down safely. How VA and watt ratings differ, which type suits which equipment, how to size one and how long its batteries last.
Computer hardware
Laptops, desktops, servers, printers, networking, UPS, software and consumables from the brands you trust.
IT downtime cost calculator
What an hour of systems being down costs your business in idle staff and lost sales.
IT health check
Twelve quick questions on backups, security, power protection, equipment and support. Enter your email and phone number at the end to see your score and a list of your gaps with practical fixes, and we email you the action plan.
CCTV storage calculator
How much hard disk your cameras need for the number of days of recording you want to keep.
Printer cost per page calculator
Compare the real cost per page of two printers, counting toner or ink and paper.
Want exact figures for your business?
Send us your numbers and the Powercomputers team will come back with options and a quote.